Santoso, Didik (2020) Analisa Keandalan SUTM 20KV Penyulang Ketapang Di PLN Gedangan. Undergraduate thesis, Universitas 17 Agustus 1945 Surabaya.
Text
ABSTRAK.pdf Download (613kB) |
|
Text (BAB I)
Bab I.pdf Restricted to Registered users only Download (362kB) | Request a copy |
|
Text (BAB II)
Bab II.pdf Restricted to Registered users only Download (1MB) | Request a copy |
|
Text (BAB III)
Bab III.pdf Restricted to Repository staff only Download (558kB) | Request a copy |
|
Text (BAB IV)
Bab IV.pdf Restricted to Repository staff only Download (1MB) | Request a copy |
|
Text (BAB V)
Bab V.pdf Restricted to Repository staff only Download (370kB) | Request a copy |
|
Text
Lampiran.pdf Download (1MB) |
|
Text
Jurnal.pdf Download (209kB) |
|
Text
Jurnal Turnitin.pdf Download (1MB) |
Abstract
Penelitian ini bertujuan untuk mengevaluasi jaringan distribusi 20Kv PT. PLN (Persero) Rayon Gedangan Penyulang Ketapang menggunakan indeks keandalan SAIFI dan SAIDI. Indeks keandalan dihitung menggunakan metode Section Technique untuk menghitung laju kegagalan komponen dan jam per tahun pada tiap Sectionnya. Hasil evaluasi nilai SAIFI terbesar untuk Penyulang Ketapang ada diSection 2 :1.45066409 gangguan/tahun dan nilai SAIDI terbesar ada diSection 8 : 2.26020193 jam/tahun. Agar terlihat andal perlu melakukan pemeliharaan seperti halnya maintenance trafo, memotong pohon disekitar jaringan untuk menghindari jaringan bersentuhan dengan pohon.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | Keandalan, sistem distribusi, SAIFI, SAIDI |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Fakultas Teknik > Program Studi Teknik Elektro |
Depositing User: | Didik Santoso |
Date Deposited: | 09 Aug 2020 03:35 |
Last Modified: | 18 Jul 2022 07:44 |
URI: | http://repository.untag-sby.ac.id/id/eprint/4544 |