Analisa Keandalan SUTM 20KV Penyulang Ketapang Di PLN Gedangan

Santoso, Didik (2020) Analisa Keandalan SUTM 20KV Penyulang Ketapang Di PLN Gedangan. Undergraduate thesis, Universitas 17 Agustus 1945 Surabaya.

[img] Text
ABSTRAK.pdf

Download (613kB)
[img] Text (BAB I)
Bab I.pdf
Restricted to Registered users only

Download (362kB) | Request a copy
[img] Text (BAB II)
Bab II.pdf
Restricted to Registered users only

Download (1MB) | Request a copy
[img] Text (BAB III)
Bab III.pdf
Restricted to Repository staff only

Download (558kB) | Request a copy
[img] Text (BAB IV)
Bab IV.pdf
Restricted to Repository staff only

Download (1MB) | Request a copy
[img] Text (BAB V)
Bab V.pdf
Restricted to Repository staff only

Download (370kB) | Request a copy
[img] Text
Lampiran.pdf

Download (1MB)
[img] Text
Jurnal.pdf

Download (209kB)
[img] Text
Jurnal Turnitin.pdf

Download (1MB)

Abstract

Penelitian ini bertujuan untuk mengevaluasi jaringan distribusi 20Kv PT. PLN (Persero) Rayon Gedangan Penyulang Ketapang menggunakan indeks keandalan SAIFI dan SAIDI. Indeks keandalan dihitung menggunakan metode Section Technique untuk menghitung laju kegagalan komponen dan jam per tahun pada tiap Sectionnya. Hasil evaluasi nilai SAIFI terbesar untuk Penyulang Ketapang ada diSection 2 :1.45066409 gangguan/tahun dan nilai SAIDI terbesar ada diSection 8 : 2.26020193 jam/tahun. Agar terlihat andal perlu melakukan pemeliharaan seperti halnya maintenance trafo, memotong pohon disekitar jaringan untuk menghindari jaringan bersentuhan dengan pohon.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Keandalan, sistem distribusi, SAIFI, SAIDI
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering